Difference between revisions of "Vertex Multi-Point Toxic Gas Monitoring System"

From LNF Wiki
Jump to navigation Jump to search
Line 4: Line 4:
 
|caption= Vertex Multi-Point Toxic Gas Monitoring System
 
|caption= Vertex Multi-Point Toxic Gas Monitoring System
 
|materials = Amine, Chlorine, Fluorine, Hydride, Mineral Acid
 
|materials = Amine, Chlorine, Fluorine, Hydride, Mineral Acid
|Monitoring = Extractive
+
|Monitoring = Extraction
 
|gases = One system monitors up to nine gas families and more than 40 gases
 
|gases = One system monitors up to nine gas families and more than 40 gases
 
|overview = []
 
|overview = []

Revision as of 11:21, 10 March 2020

< Life Safety Systems

Vertex Multi-Point Toxic Gas Monitoring System
Vertex Multi-Point Toxic Gas Monitoring System
Equipment Details
Technology [[]]
Materials Restriction Undefined
Material Processed Amine, Chlorine, Fluorine, Hydride, Mineral Acid
Gases Used One system monitors up to nine gas families and more than 40 gases
Equipment Manual
Overview []
Operating Procedure SOP



Capabilities

Detect more than 40 Toxic Gases Sampling points can be up to 400 feet (120 meters) from the system. There is a choice of universal analyser modules and/or pyrolyzer analyzers. Simplified replacement of Chemcassettes® and automated optics verification

System Overview

The LNF has three Vertex systems spread across the lab to reach it's more than 150 points. Vertex one and two are located in 1445S. Vertex three is located in 14C10. Quarter inch PTFE tubing is run to sample locations locations across the EECS and LNF to sample the working environment.

Hardware Details

Supported Processes

  1. Read through the Detailed Operating Procedure.
  2. Maintnenace is recorded and tracked in the [LSS Maintenance] document in the Drive folder.

Annual Maintenance Includes

  • Chemcassette Change
  • Air Flow Calibration
  • Filter Change
  • Pump Switch-over